Key Specifications/ Special Features:
Applicable scope and purpose
● Short -circuit protection
● Over-load protection
● Control
● Isolation
● DC system protection
NDB2T-63 (UL489) destiné aux réseaux de distribution électrique basse tension dans les secteurs de l'industrie, du bâtiment, de l'énergie, des télécommunications et des infrastructures.
Main technical specification
● Electrical parameters
○ Rated working voltage and relevant breaking capacity:
Pole
1P
2P
3P
1P
2P
3P
Rating current
1~32A
35~63A
Item
Icu
Voltage
AC 120V
10kA
—
—
10kA
—
—
AC 240V
—
10kA
10kA
—
10kA
10kA
AC 277V
10kA
—
—
—
—
—
AC 480Y/277V
—
10kA
10kA
—
—
—
DC60V
10kA
10kA
—
10kA
10kA
—
DC125V
—
10kA
—
—
10kA
—
○ Impulse withstand test voltages: 4kV
○ electrical endurance: 10000 times;Mechanical endurance: 20000 times
● Product certification and implementation standard.:
○ Product certificate:UL489;
○ Product certification standard:UL489;
● Environmental requirements:RoHS
● Isolation function
○ Practical breaking instructions
○ View window within the green identification said contact in the off position
● Tripping characteristic B type curve
○ Protection of short circuit current small load
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 4In(1±20%) C type curve
○ Protect normal load and distribution wire cable
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping range 8In(1±20%) D type curve
○ Protect starting current big impact load(Such as motor, transformer)
○ rated current:1A~63A
○ tripping characteristic:The instantaneous tripping rang 12In(1±20%)
5、Normal working environment
● Ambient temperature:-40℃~+70℃
● Air relative humidity:≤95%
● Altitude:≤2000m
● pollution degree: 3
● Service place without significant vibration and impact
Applications: The NDG3V-250~800 series switch-disconnectors are applicable to electric systems with a rated voltage up to DC 1500V and a rated current up to 800A. It can be used for infrequent close and open, it provides isolation and breaking ...
1. Applicable Scope and Purpose The NDQ3-800 P-grade ATSE are applicable for sites with the AC voltage below AC380V.AC400V.AC415V and the rated frequency of 50Hz. This product complies with the GB14048.1-2012 and GB/T14048.11-2016 standards in acc...
1.Application Scope NDB1-40 dedicated to the low voltage power distribution system of industrial, buildings, energy, communications and infrastructure. The MCB can cut off phase and neutral lines at the same time, whereas the neutral line should...